Tridium’s Niagara Edge 10 is an IP-based field equipment controller powered by the Niagara Framework. Niagara Edge 10 controllers drive applications such as zone temperature control, and the operation of fan coil units, single-stage air handling units,water-source heat pumps and more. Niagara Edge 10 controllers run the full Niagara stack, with 10 points of on-board IO and IO-R-34 expansion capability. Niagara Edge 10 licensing supports three devices and 50 total points to harness the full power of Niagara at the edge. Requires Niagara 4.7 or later. 

niagara_edge_10

NETWORK

• Niagara Edge 10 controllers can be daisy chained to continue network
connectivity and eliminate the need for separate wiring back to a switch
• Connect Niagara Edge 10 controllers to your main building or IT network
and manage them directly with a Supervisor alongside of a JACE®
• Use the secondary Ethernet port of the JACE 8000 to create a private
network of Niagara Edge 10 controllers

MOUNTING

Support mounting on EN50022 standard 7.5mm x 35mm DIN rail
or panel mounting

AGENCY CERTIFICATIONS

• FCC Part 15, class b
• C-UL
• CE
• UL916, Open Energy
Management Class 2
• RoHS2
• REACH
• WEEE
• CAN/CSA-C22.2 No. 205-12

ENVIRONMENTAL SPECIFICATIONS

Operating temperature:
-20 to 60°C
• Storage temperature: -40 to 85°C
• Humidity: 5-95% non-condensing
• Shipping & vibration: ASTM
D4169, Assurance Level II
• MTBF: 10 years

HARDWARE

NXP iMX6 SoloX2: 800 MHz ARM
Cortex-A9/M4
512 MB DDR SDRAM
2GB total eMMC flash storage
with user space set at 1GB
Powered from 24VAC/DC source
5 Universal inputs: Type 3
(10K) thermistors, 0-100K ohm,
0-10VDC, 0-20mA with external
resistor, Dry Contact
2 Analog outputs: 0-10VDC, 4mA
max output current
3 Digital outputs: Triac, 24VAC
@.5 amp
2 10/100MB Ethernet ports
capable of daisy chaining
1 RS-485 serial port
Real-time clock
Secure boot

EXPANDABILITY

One (1) IO-R-34 connected over a
shielded 485 bus

CONNECTIVITY

When data from external sources
— i.e. thermostats, variable speed
drives, or smart sensors — is
required to drive an application,
the Niagara Edge 10 allows for
connections to those types of
external sources using BACNet/
IP, Modbus, and SNMP over an
IP network and/or BACnet and
Modbus over a 485 network.

Niagara Edge 10 field controller with 10 points of onboard IO, 1 RS-485 serial port, and 2 10/100 Ethernet ports. Supports 1 IO-R-34. Includes Niagara N4 and drivers for BACnet, Modbus, and SNMP. Supports up to 3 devices or 50 points. Includes all software updates released for commercial use by Tridium for the life of N4, but not for any later versions.